【焦点问题】某大型BC船锅炉层配置20L轻水泡沫及备用泡沫桶,近期被开出此泡沫装置不能立即使用,理由是在配置foam applicator 的甲板层没有消防栓,并要求检验,而实船配置:在下一层的消防栓距离此泡沫装置不到5米距离,从锅炉层通过A60门到走廊约6米左右,此门外有消防栓,请问检查人员开此缺陷是否正确?为什么?
【规范/公约依据】
SOLAS - Chapter II-2 - Construction - Fire protection, fire detection and fire extinction - Part C - Suppression of fire - Regulation 10 - Fire fighting
5.2.2 Additional fire-extinguishing arrangementsfootnote
5.2.2.1 There shall be at least one portable foamapplicator unit complying with the provisions of the Fire Safety Systems Code.
FSS Code - Resolution MSC.98(73) - Annex - International Code For Fire Safety Systems - Chapter 4 - Fire Extinguishers - 3 Engineering specifications
3.2 Portable foam applicators
3.2.1 A portable foam applicator unit shall consist of a foam nozzle/branch pipe, either of a self-inducingtype or in combination with a separate inductor, capable of being connected to the fire main by a fire hose, together with a portable tank containing at least 20 ⋉ of foam concentrate and at least one spare tank of foam concentrate of the same capacity.
【争议观点】
● 类似问题较为常见。船员可以解释成,可以移动使用。保证一切应急设备立即可用即可。
● 目前是foam applicator 储存位置没有消防栓,那应看距离多远,评估下是否符合立即可用。按照公约要求,能够连接到主消防管即可。
● portable form applicator意思是可以手提着移动的,哪里着火就提到哪去,很多船是放在集控室门口,就是为了方面寻找,并不是必须要接集控室门口的消防栓。
● 这也是一方面,另一方面是安放在锅炉层或发电机组层,主要考虑此处着火危险较高的原因。
● 那就要看现场是不是能比较快速的在锅炉层连接使用了。SOLAS公约第II-2 章第10条 5.1.2.1 规定:每一锅炉舱内或锅炉舱入口外侧应至少设有1套符合《消防安全系统规则》规定的手提泡沫枪装置。
● 锅炉舱和机舱一体的话,一套就够了严格地讲。
● 原来机舱一般2套,最近SOLAS是不是取消了1套?没变化。变化的是135L的规定。详见MSC.409(97)
【结论】
● 从船舶机舱消防栓实际布置来看,从下一层到20L灭火剂位置不到5米左右,空全满足灭火功能,满足公约要求,无需再增加额外的消防栓。
● 主要是没有对现场进行实地有效评估,开出缺陷欠妥,同时也反映出船长及陪检人员不能及时对缺陷提出异议,及时让检查人员取消缺陷!